Table 2 Dust concentration limit in the equipment room
Substance Concentration limit (
p
articles/m
3
)
Dust particles
3 x 10
4
(No visible dust on desk in three days)
NOTE:
Dust particle diameter 5 μm
To eliminate corrosion and premature aging of components, the equipment room must also meet limits on
salts, acids, and sulfides, as shown in Table 3.
Table 3 Harmful gas li
mits in an equipment room
Gas Max. (m
g
/m
3
)
SO
2
0.2
H
2
S 0.006
NH
3
0.05
Cl
2
0.01
Cooling
The device uses left to right airflow for heat dissipation. Plan the installation site for adequate ventilation.
H3C recommends that you leave a minimum of 10 cm (3.94 in) of clearance around the air vents.
Make sure the rack is well ventilated.
Figure 1 Airflow through the device chassis
ESD prevention
To prevent electrostatic discharge (ESD), follow these guidelines:
Ground the device properly.
Take dust-proof measures for the equipment room. For more information, see "Cleanness."
Maintain the humidity and temperature at a proper level. For more information, see "Temperature
and h
umidity."